FZX-ACT2/3/4/5/5.5/7/1.2-ZY
1, simple structure, reliable performance and easy installation.
2, it can be used for total submersion fire extinguishing in closed spaces, and can also be used for partial application fire extinguishing in open places.
The fire extinguishing device mainly consists of a suspension cylinder, a gas head, a spring pressure gauge, a lifting ring, etc. Filling in the hanging cylinderABCUltra-fine dry powder fire extinguishing agent, the driving gas is nitrogen.
| Specifications and models | FZX-ACT2/1.2-ZY | FZX-ACT3/1.2-ZY | FZX-ACT4/1.2-ZY | FZX-ACT5/1.2-ZY | FZX-ACT5.5/1.2-ZY | FZX-ACT7/1.2-ZY | |
| Fire extinguishing dose (Kg) | 2+0.1 | 3+0.15 | 4+0.2 | 5+0.25 | 5.5+0.275 | 7+0.35 | |
| Protection space (m3) | 16 | 25 | 36 | 45 | 45 | 80 | |
| Fire extinguishing device height (mm) | 280 | 335 | 317 | 337 | 337 | 380 | |
| Diameter of fire extinguishing device (mm) | 235 | 235 | 310 | 310 | 310 | 320 | |
| Maximum installation height (m) | ≤3 | ≤3 | ≤4 | ≤6 | ≤6 | ≤8 | |
| Injection remaining rate (%) | ≤5 | ||||||
| Injection time (s) | ≤5 | ≤10 | |||||
| Working pressure (Mpa) | 1.25±0.05 | ||||||
| Maximum working pressure (Mpa) | 1.4 | ||||||
| Water test pressure (Mpa) | 2.1 | ||||||
| Operating temperature range (℃) | -10~50 | ||||||