EVFH-TCQ03-ZY
The alarm device consists of a detection unit, a control unit and a display unit. This product monitors early fire hazards and fires in the lithium battery box in real time, sends out audible and visual alarm messages to the driver in a timely manner, and triggers fire extinguishing automatically/manually to suppress fires in the battery box. It integrates hidden danger reporting, fire identification, and emergency fire extinguishing.
The product is small in size, easy to install, and the installation method is flexible. An adapter board can be added according to user needs to flexibly change the installation size. The product's operating voltage range is DC9 ~ 36V, and the power supply mode can be adopted to provide nearby power supply, reducing installation location restrictions.
The product has a CO concentration display. You can select "03 Read Data" in the main menu, then select the corresponding detection unit address (default is 01), press the "Confirm" key to read the data, and display the currently detected CO concentration value in real time. The user can intuitively and quickly understand the current CO concentration value in the battery box.
| serial number | Project | unit | Technical indicators |
| 1 | Device model | — | EVFH-TCQ03-ZY |
| 2 | Implementation standards | Q/JSZY 006-2021 | |
| 3 | Rated working voltage | V | DC 24 |
| 4 | Working voltage range | V | DC9~36 |
| 5 | Inspection current | mA | ≤120 (taking District 10 as an example) |
| 6 | Rated working pressure of bottle group | MPa | 12.5 |
| 7 | Fire extinguishing media type | Special gas fire extinguishing agent for lithium batteries | |
| 8 | Fire extinguishing agent quality | Kg | 4.8 |
| 9 | Fire extinguishing agent spraying time | s | 60≤t≤120 |
| 10 | Fire extinguishing time | s | Minimum 10 |
| 11 | Operating temperature range | ℃ | -40~+85 |
| 12 | Working environment humidity | RH | ≤95% |
| 13 | Temperature alarm range | ℃ | 72 |
| 14 | Carbon monoxide alarm setting value | (volume fraction) | 190×10-6 |
| 15 | Gas sensor life | year | 3 |
| 16 | Fire extinguishing agent spray form | Total submergence balanced injection | |
| 17 | Communication line system | CAN bus | |
| 18 | System startup method | — | Automatic, electric manual and manual emergency |
| 19 | Number of battery boxes that can be protected | a | 1~10 (optional, expandable) |
| 20 | Reserved I/O ports | GPS/GIS/BMS/RMC/Test/Flash Rom | |
| 21 | Dimensions | mm | Control unit: 193 (L) × 153 (W) × 30 (H) Detection unit: 82.2 (L) × 65.5 (W) × 22.5 (H) Display unit: 126.2 (L) × 61.5 (W) × 16 (H) |