• Non-storage pressure perfluorohexanone fire extinguishing device (piston type)
  • Non-storage pressure perfluorohexanone fire extinguishing device (piston type)

HFYF-0.3Q/0.5Q/1Q/1.5Q/2Q-ZY

Non-storage pressure perfluorohexanone fire extinguishing device (piston type)

1.Product overview

  The non-storage pressure perfluorohexanone fire extinguishing device (piston type) fire extinguishing agent adopts a new high-efficiency cooling and environmentally friendly material - perfluorohexanone, which has the advantages of high fire extinguishing efficiency, good environmental performance, non-toxic, non-polluting air, and no corrosion to the human body and batteries. It can be used in small energy storage cabinets, industrial and commercial energy storage power stations, data centers, communication rooms, power equipment rooms and other places.

2.Product features

1. Slender body shape: small size, easy to arrange and install;

2. Efficient fire extinguishing: use highly efficient and environmentally friendly perfluorohexanone fire extinguishing agent;

3. The direction of the nozzle is adjustable: the direction of the nozzle can be freely adjusted 360°;

4. Atomizing nozzle: The device comes with an atomizing nozzle, which has fine mist droplets, fast heat absorption, and high cooling efficiency;

5. The structure is simple and easy to install: it can be combined with a thermal wire to form a simple system that can automatically start at 170°C. There is no pipeline, no linkage, no need for holes, and it is simple and easy to install;

6. Expandability: With communication control cabinet, alarm can be activatedAutomatic module, temperature, smoke, hydrogen and CO detectors, etc., can be started manually or automatically.


1. Technical parameters

ProjectParameters
Specifications and modelsHFYF-0.3Q-ZYHFYF-0.3Q-ZYHFYF-0.3Q-ZYHFYF-0.3Q-ZYHFYF-0.3Q-ZY
Device weight (kg)1.82.33.64.75.7
Operating temperature range-40~70℃
Working humidity≤95%
Types of fire extinguishing agentsPerfluorohexanone fire extinguishing agent
Fire extinguishing agent filling amount (g)300500100015002000
Protection space (m³)0.40.61.322.9
Start modeElectric control, temperature control
Injection time (s)≤2≤4≤6≤12≤20
Electrical initiator resistance (Ω)2.4~3.3
Safety current (mA)≤150
Starting current (mA)≥380
Use voltage (V)DC9~24
Product expiration date5 years

2. Specifications and dimensions

Specifications and modelsHFYF-0.3Q-ZYHFYF-0.5Q-ZYHFYF-1Q-ZYHFYF-1.5Q-ZYHFYF-2Q-ZY
A380481453564674
B8383939393
C8080100100100
D6868888888
E303404376487579