• Hydrogen, carbon monoxide and smoke and temperature sensing composite fire detection devices for energy storage power stations

ESTC401-ZY

Hydrogen, carbon monoxide and smoke and temperature sensing composite fire detection devices for energy storage power stations

ESTC401-ZY hydrogen, carbon monoxide and smoke and temperature composite fire detection device for energy storage power stations is mainly used for thermal runaway monitoring of energy storage cabins in energy storage power stations, and generally works together with linked control cabinets. It will monitor the carbon monoxide, hydrogen, smoke concentration and temperature data in the environment, and then analyze the data to determine whether there is a battery thermal runaway phenomenon. It can detect early fires in time and link external firefighting equipment to respond to avoid the expansion and spread of fires.

1. Product features

1. Using high-sensitivity sensors, changes in temperature, smoke concentration, hydrogen, and carbon monoxide concentrations in the energy storage power station area can be detected before a fire occurs.

2. Collect and monitor the air environment in the environment in real time. When changes in temperature and gas concentration occur, the equipment will respond immediately.

3. It adopts CAN bus communication and is easy to wire. It can be connected to other functional equipment.

4. Accurately monitor the gas in the energy storage cabin to prevent false alarms and omissions.

5. Three status indicators, the device has a self-test function, which can prompt the functional status of the device itself.

2. Usage environment

a) Working temperature: -10℃~+55℃;

b) Relative humidity:

c) Working voltage: DC 24V;

d) Working current: 10 mA;

e) Wind speed: no more than 8m/S.

3. Product parameters

Product nameHydrogen, carbon monoxide and smoke-sensing and temperature-sensing composite fire detection devices for energy storage power stations
Product modelESTC401-ZYImplementation standardsQ/JSZY ESTC401-2023
Communication typeCAN busDetection objectHydrogen, carbon monoxide, smoke and temperature
carbon monoxideAlarm setting value: 190*10-6 volume fraction Range: (0~500)*10-6 volume fraction
HydrogenAlarm setting value: 200*10-6 volume fraction Range: (0~500)*10-6 volume fraction
Temperature sensing typeCategory BWorking parametersDC24V
Appearance size91x65x27(mm)Sensor life≤3 years
InstallationWall installationoutputDC24V